Installation
28│Page
Inordertopurgeairinwaterpipeswithinaclosed‐loopsystem,anairvent
andairseparatorshouldbeinstalledintothesystem.Requiredcirculation
flow rates are labeled next to each application diagram.These flow rate
requirementsmustbefollowed.
Toxicchemicalsusedin boiler
treatmentssuchasalcohol,glycerolandglycol
groupsmustnotbeintroducedintothesystemifthesystemincorporatesan
open‐looppotablewatersystem.
Thewaterheatercanbeusedtosupplypotablewaterandspaceheatingand
shall not be connected to any heating system or component(s)
previously
usedwithnon‐potablewaterwhereanychemicalswereaddedtothewater
heatingappliances.
When the system requires water for space heating at temperatures higher
than required for other uses, a means such as a mixing valve shall be
installed to temper thewater forthose other uses
in orderto reducescald
hazardpotential.
Water temperature over 125°F (52°C) can cause severe burns instantly or
deathfromscalds.
ChemicalssuchasdilutedGlycolcanbeusedforradiantfloor,Hy dro/fancoil
air or Baseboard heating only. The diluted solution of glycol must contain
between25
and55%ofGlycol.Beawarethatinclosed‐loopglycolsystems,
low pressure in the heat exchanger can cause low‐temperature boiling,
resulting in excessive noise and damage to the water heater. Consult with
theglycolmakerforspecificationspriortouse.
Thisisaco nceptdrawingonly.
APPLICATIONS
‐Space‐HeatingApplications‐
*Therecirculationpumpistobecontrolledby:
‐Dual‐setaquastat(recommendedw/timer)
OR
‐“PumpControlConnections”510(T‐D2)modelsonly.
Refertop.23.
*Therecirculationpumpistoprovidenolessthan2
GPMandnomorethan4GPMthrougheach
activatedunitin
thesystem.
‐Recirculation‐
WARNING
Pressure
reliefvalve
Checkvalve
Checkvalve
Air
se
arator
Recirculation
um
Hotwateroutletto
fixtures
AirVent
Unions
Gassupply
Ballvalves
Expansiontank
Y‐Strainer
Coldwater
inlet
Hot
Water
Outlet
S
Cold
Water
Inlet
Gas
Inlet