Installation
23Page
InanEasyLinksystem,thepumpmustbeconnectedtothe“Pump”connectorin
the“PARENT”unitonly.Ifthepumpiscon nectedtoanyofthe“CHILD”units,the
pumpwillnotwork.
PUMPCONTROLCONNECTIONS
Availableonthe510(TD2)modelsonly
The510(TD2)modelswaterheaterscanbeusedtocontrolarecirculationpump.Properpumpcontrol
helpstopreservethelifeofthesystemandsavesenergyaswell.
Thewaterheaterpumpcontrolportisa“normally opendrycontact”,andthereforeneedsadditional
components to properly
control a recirculation pump. To control a recirculation pump, connect the
pump to the “Pump” connector in the water heater as shown in the diagram below. (In an EasyLink
system, connect the pump ONLY to the PARENT unit.) The pump is to be connected using suitable
relaysshown
inthediagrambelow.
Pleasemakesuretherelaysareproperlyratedfortherecirculationpump.
Usingthewaterheater’sinternalthermistorsasatemperaturecontrol,therecirculationpumpwill only
turnonwhenrecirculationisneeded.
CAUTION
ThesecomponentsareNOTincludedwiththewaterheaterandare
externaltotheunit.Theymustbeacquiredseparately.
Connectto this“Pump connector”.
Recirculation
pump
Thermal
relay
120VAC
220VACetc
forrelay
Powersupply
forpump
120VAC
220VACetc
Powersupply
forrelay